By-pass insert - short-circuit part RXV 05/300
Dimensions: 537 x 312 x 300 mm replacement for exchanger: RX 05/300, RX-P 05/300 material: plastic
We offer a wide range of enthalpy exchangers suitable for most heat recovery units. If you can't find the right model, don't hesitate to contact us – we will be happy to help!
Flow rate 570m3/hour - Efficiency 95.2% ....
Flow rate 350m3/hour - Efficiency 95.5% ....
Flow rate 105 m3/hour - Efficiency 96.2% ....
Dimensions: 537 x 312 x 300 mm ....
Weight: 6.12 kg ....
Material: aluminum
RX and RX-P are modern counter-flow exchangers with fins made of durable aluminum and plastic. The counter-flow exchanger is the successor to the less efficient cross-flow exchanger. The counter-flow exchanger does not transmit moisture or odors. Its efficiency exceeds 95%.
It is thanks to these properties, together with the tested tightness of each manufactured piece, that it finds its use both in heat recovery units of passive houses and in industrial applications.
Upon request, we will send you complete exchanger parameters and resulting values by e-mail in the form of parameter sheets in .pdf format, under your desired conditions (humidity, temperature, air volume flow).
Efficiency of RX counterflow exchangers
Graph of pressure loss - PD [Pa] versus volume flow AV [m3/h] - RX 05/300 exchanger
Parameters for the average winter period in the Czech Republic
indoor/outdoor air ratio 1:1, outdoor air temperature 1°C and relative humidity 78%, indoor air temperature 25°C and relative humidity 28%, results from calculation software certified by the European company Eurovent
Graph of the dependence of efficiency EFF [%] on volume flow AV [m3/h] - exchanger RX 05/300
Parameters for the average winter period in the Czech Republic
indoor/outdoor air ratio 1:1, outdoor air temperature 1°C and relative humidity 78%, temperature inindoor air 25°C and relative humidity 28%, results from calculation software certified by the European company Eurovent
The heat recovery exchanger can be installed in any position in the unit (cabinet, box).
Installation on a narrow tray. Recommended slope of 3° to the waste heat outlet for good condensate drainage. | |
Installation on the front surface Recommended slope of 5° to the waste heat outlet for good condensate drainage. | |
Installation on a narrow tray This position is only possible if the entire weight of the exchanger does not rest on a narrow tray. |
Thanks to the precise processing of the exchanger dimensions, their mutual combination is possible to increase efficiency and maximum air flow.
The fins of the entire RX heat exchanger range are equipped with double-flange technology, achieving the best tightness on the market.
In order to respond to your orders as quickly as possible, we keep the most popular exchangers in stock in larger quantities.
If you do not choose from our offer in the e-shop, there is no problem for us to price you any exchanger according to the table below.
Data sheet
Dimensions: 537 x 312 x 300 mm replacement for exchanger: RX 05/300, RX-P 05/300 material: plastic